Parameter 16-85 FC Port CTW 1
Table 898: Parameter 16-85 FC Port CTW 1
16-85 FC Port CTW 1
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: V2
Change during operation: False
View the 2-byte control word (CTW) received from the fieldbus master. Interpretation of the control word depends on the fieldbus
option installed and the control word profile selected in parameter 8-10 Control Word Profile.
Parameter 16-86 FC Port REF 1
Table 899: Parameter 16-86 FC Port REF 1
16-86 FC Port REF 1
Default value: 0
Parameter type: Range, -200 - 200
Setup: All setups
Conversion index: 0
Data type: N2
Change during operation: False
View the 2-byte status word (STW) sent to the fieldbus master. Interpretation of the status word depends on the fieldbus option
installed and the control word profile selected in parameter 8-10 Control Word Profile.
Parameter 16-87 Bus Readout Alarm/Warning
Table 900: Parameter 16-87 Bus Readout Alarm/Warning
16-87 Bus Readout Alarm/Warning
Default value: 0
Parameter type: Range, 0 - 65535, Array [3]
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
Alarm and warning numbers in hex as shown in the alarm log. The high byte contains the alarm, the low byte contains the warning.
The alarm number is the 1
st
that occurred after the last reset.
Parameter 16-88 Fieldbus Torque FF
Table 901: Parameter 16-88 Fieldbus Torque FF
16-88 Fieldbus Torque FF
Default value: 0
Parameter type: Range, -200 - 200
Setup: 1 setup
Conversion index: 0
Data type: N2
Change during operation: True
A PCD write reference parameter. This parameter allows the PLC to adjust the Torque FF over the fieldbus continuously as a per-
centage of motor nominal torque, see parameter 1-26 Motor Cont. Rated Torque.
Parameter 16-89 Configurable Alarm/Warning Word
Table 902: Parameter 16-89 Configurable Alarm/Warning Word
16-89 Configurable Alarm/Warning Word
Default Value: 0
Parameter Type: Range, 0 - 65535
Setup: All setups
Conversion Index: 0
Data Type: Uint16
Change during operation: False
This alarm/warning word is configured in parameter 8-17 Configurable Alarm and Warningword to match the actual requirements.
5.16.7 16-9* Diagnosis Readouts
For details of bit descriptions, refer to Table 1436.
AU275636650261en-000101 / 130R0334 | 513Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals