Parameter 18-04 Mech Brake Count
Table 970: Parameter 18-04 Mech Brake Count
18-04 Mech Brake Count
Default value: 0
Parameter type: Range, 0 - 4294967295
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: False
Number of occurrences the mechanical brake is engaged.
5.18.2 18-1* Emergency Mode Log
The emergency log covers operation of emergency mode with start and stop activities and if critical alarms are suppressed during
emergency mode. The log contains the 10 latest activations of emergency mode or the alarm number of the critical alarm that was
suppressed as this affects the warranty of the drive. Suppressed alarm numbers are stored and can only be reset by a Danfoss serv-
ice inspection.
Parameter 18-10 Emergency Mode Log: Event
Table 971: Parameter 18-10 Emergency Mode Log: Event
18-10 Emergency Mode Log: Event
Default value: 0
Parameter type: Range, 0 - 255, Array [10]
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
This parameter contains an array with 10 elements. The number read represents a fault code, which corresponds to a specific alarm.
Refer to 7.1.2 Alarm/Warning Code List.
Parameter 18-11 Emergency Mode Log: Time
Table 972: Parameter 18-11 Emergency Mode Log: Time
18-11 Emergency Mode Log: Time
Default value: 0 s
Parameter type: Range, 0 - 2147483647 s, Array [10]
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: False
This parameter shows at which time the logged event occurred. Time is measured in seconds since the drive was started.
Parameter 18-12 Emergency Mode Log: Date and Time
Table 973: Parameter 18-12 Emergency Mode Log: Date and Time
18-12 Emergency Mode Log: Date and Time
Default value: Size related
Parameter type: Range, Size related, Array [10]
Setup: All setups
Conversion index: 0
Data type: TimeOfDay
Change during operation: False
This parameter shows at which date and time the logged event occurred. The date and time rely on the internal clock in parameter
group 0-7* Clock Settings.
5.18.3 18-1* Parameter Log
Parameter 18-13 Parameter Number
Table 974: Parameter 18-13 Parameter Number
18-13 Parameter Number
Default value: 0 N/A
Parameter type: Range, 0 - 0xFFFF N/A, Array [10]
4-setup: All set-ups
Conversion index: 0
Data type: Uint16
Change during operation: False
Shows the parameter which is most recently changed. Index 0 shows the latest change in the parameter.
AU275636650261en-000101 / 130R0334 | 539Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals