5.9.3 8-2* Counters
Parameter 8-20: Invalid Memory Write Counter
Table 508: Parameter 8-20: Invalid Memory Write Counter
8-20: Invalid Memory Write Counter
Default value: 0
Parameter type: Range (0 - 65535)
4-setup: 1 setup
Conversion index: -
Data type: Uint8
Change during operation: True
5.9.4 8-3* FC Port Settings
Parameter 8-30 Protocol
Table 509: Parameter 8-30 Protocol
8-30 Protocol
Default value: [0] FC
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
Select the protocol to be used. Changing protocol is not effective until after powering off the drive.
Option
Name
Description
[0]*
FC
[1]
FC MC
[2]
Modbus RTU
Parameter 8-31 Address
Table 510: Parameter 8-31 Address
8-31 Address
Default value: 1
Parameter type: Range, 1 - 247
Setup: 1 setup
Conversion index: 0
Data type: Uint8
Change during operation: True
Enter the address for the drive (standard) port. Valid range: Depends on the selected protocol.
Parameter 8-32 FC Port Baud Rate
Table 511: Parameter 8-32 FC Port Baud Rate
8-32 FC Port Baud Rate
Default value: Size related
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[0]
2400 Baud
Baud rate selection for the FC (standard) port.
[1]
4800 Baud
[2]
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
AU275636650261en-000101 / 130R0334 | 287Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide