Parameter 30-99 Wifi Network Mode
Table 1103: Parameter 30-99 Wifi Network Mode
Default value: [1] Access point
Change during operation: True
5.24 Parameter Group 31-** Bypass Option
N O T I C E
This parameter group is only available in FC 302.
Parameter 31-00 Bypass Mode
Table 1104: Parameter 31-00 Bypass Mode
Change during operation: True
Select the bypass operating mode.
The drive operates the motor.
The motor is operated at full speed during bypass mode.
Parameter 31-01 Bypass Start Time Delay
Table 1105: Parameter 31-01 Bypass Start Time Delay
31-01 Bypass Start Time Delay
Parameter Type: Range, 0 - 60 s
Change during operation: True
Setting the time delay to pass from the bypass receives a run command until it starts the motor at full speed. A countdown timer
shows the remaining time.
Parameter 31-02 Bypass Trip Time Delay
Table 1106: Parameter 31-02 Bypass Trip Time Delay
31-02 Bypass Trip Time Delay
Parameter type: Range, 0 - 300 s
Change during operation: True
AU275636650261en-000101 / 130R0334586 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide