4.1.6 Initial Commissioning
The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick setup procedure us-
ing LCP 102 (read the following table from left to right). The example applies to open-loop applications.
Table 3: Quick Setup Procedure
Press
Q2 Quick Menu.
Parameter 0-01 Language
Set language.
Parameter 1-20 Motor Power [kW]
Set motor nameplate power.
Parameter 1-22 Motor Voltage
Set nameplate voltage.
Parameter 1-23 Motor Frequency
Set nameplate frequency.
Parameter 1-24 Motor Current
Set nameplate current.
Parameter 1-25 Motor Nominal Speed
Set nameplate speed in RPM.
Parameter 5-12 Terminal 27 Digital In-
put
If terminal default is [2] Coast in-
verse, it is possible to change this
setting to [0] No function. No con-
nection to terminal 27 is then
needed for running AMA.
AU275636650261en-000101 / 130R033426 | Danfoss A/S © 2022.12
How to Program
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals