Parameter 1-18 Min. Current at No Load
Table 75: Parameter 1-18 Min. Current at No Load
1-18 Min. Current at No Load
Parameter type: Range, 0 - 50%
Change during operation: True
Adjust this parameter to achieve a smoother motor operation.
5.2.4 1-2* Motor Data
This parameter group contains input data from the nameplate on the connected motor.
N O T I C E
Changing the value of these parameters affects the setting of other parameters.
N O T I C E
The following parameters have no effect when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM, [2] PM, salient
IPM, [5] Sync. Reluctance:
Parameter 1-20 Motor Power [kW]
Parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-20 Motor Power [kW]
Table 76: Parameter 1-20 Motor Power [kW]
Default value: Size related
Parameter type: Range, 0.09 - 3000.00 kW
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the nominal motor power in kW according to the motor nameplate data. The default value corresponds to the nominal rated
output of the drive. This parameter is visible in the LCP if parameter 0-03 Regional Settings is set to [0] International.
Parameter 1-21 Motor Power [HP]
Table 77: Parameter 1-21 Motor Power [HP]
Default value: Size related
Parameter type: Range, 0.09 - 3000.00 hp
Change during operation: False
Enter the nominal motor power in hp according to the motor nameplate data. The default value corresponds to the nominal rated
output of the drive. This parameter is visible in the LCP if parameter 0-03 Regional Settings is set to [1] North America.
AU275636650261en-000101 / 130R0334 | 75Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide