EasyManuals Logo

Danfoss vlt FC 102 Programming Guide

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
0-20 Display Line 1.1 Small
Option: Function:
[1614] Motor current Phase current of the motor
measured as eective value.
[1615] Frequency [%] Motor frequency, that is the output
frequency from the frequency
converter in percent. The frequency
% value is based upon the
frequency in parameter 4-19 Max
Output Frequency.
[1616] Torque [Nm] Present motor load as a percentage
of the rated motor torque.
[1617] Speed [RPM] Motor speed reference. Actual
speed depends on slip compen-
sation being used (compensation
set in parameter 1-62 Slip Compen-
sation). If not used, actual speed is
the value read in the display minus
motor slip.
[1618] Motor Thermal Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
[1619] Thermistor
Sensor
Temperature
[1620] Motor Angle
[1622] Torque [%] Shows the actual torque produced,
in percentage.
[1623] Motor Shaft
Power [kW]
[1624] Calibrated
Stator
Resistance
[1626] Power Filtered
[kW]
[1627] Power Filtered
[hp]
[1630] DC Link
Voltage
Intermediate circuit voltage in the
frequency converter.
[1631] System Temp.
[1632] Brake
Energy /s
Present brake power transferred to
an external brake resistor.
Stated as an instantaneous value.
[1633] Brake Energy
Average
Brake power transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 s.
[1634] Heatsink
Temp.
Present heat sink temperature of
the frequency converter. The cut-
out limit is 95 ±5 °C; cutting back
in occurs at 70 ± 5 °C.
0-20 Display Line 1.1 Small
Option: Function:
[1635] Inverter
Thermal
Percentage load of the inverters.
[1636] Inv. Nom.
Current
Nominal current of the frequency
converter.
[1637] Inv. Max.
Current
Maximum current of the frequency
converter.
[1638] SL Controller
State
State of the event executed by the
control.
[1639] Control Card
Temp.
Temperature of the control card.
[1642] Service Log
Counter
[1643] Timed Actions
Status
See parameter group 23-0* Timed
Actions.
[1645] Motor Phase U
Current
[1646] Motor Phase V
Current
[1647] Motor Phase
W Current
[1650] External
Reference
Sum of the external reference as a
percentage, that is the sum of
analog/pulse/bus.
[1652] Feedback[Unit] Reference value from programmed
digital input(s).
[1653] Digi Pot
Reference
View the contribution of the digital
potentiometer to the actual
reference feedback.
[1654] Feedback 1
[Unit]
View the value of feedback 1. See
also parameter group 20-0* FC
Closed Loop.
[1655] Feedback 2
[Unit]
View the value of feedback 2. See
also parameter group 20-0* FC
Closed Loop.
[1656] Feedback 3
[Unit]
View the value of feedback 3. See
also parameter group 20-0* FC
Closed Loop.
[1658] PID Output
[%]
Returns the drive closed-loop PID
controller output value in percent.
[1659] Adjusted
Setpoint
[1660] Digital Input Shows the status of the digital
inputs. Signal low=0; Signal high=1.
Regarding the order, see
parameter 16-60 Digital Input. Bit 0
is at the far right.
[1661] Terminal 53
Switch Setting
Setting of input terminal 53.
Current=0; Voltage=1.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
32 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL

Related product manuals