D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 120 -
Shutdown alarm bits. Bit definitions are given at the end of the
document.
Loaddump alarm bits. Bit definitions are given at the end of the
document.
Warning alarm bits. Bit definitions are given at the end of the
document.
0= genset at rest
1= wait before fuel
2= engine preheat
3= wait oil flash off
4=crank rest
5=cranking
6= engine run idle speed
7= engine heating
8= running off load
9= synchronizing to mains
10= load transfer to genset
11= gen cb activation
12= genset cb timer
13= master genset on load,
14= peak lopping
15= power exporting
16= slave genset on load
17= synchronizing back to mains
18= load transfer to mains
19= mains cb activation
20= mains cb timer
21= stop with cooldown
22= cooling down
23= engine stop idle speed
24= immediate stop
25= engine stopping
0= STOP mode
1= AUTO mode
2= MANUAL mode
3= TEST mode
Genset operation timer. In various wait statuses, the genset
operation status will change at the expiration of this timer.
Device hardware version information
Device software version information
Counter: number of genset runs
Counter: number of genset cranks
Counter: number of genset on load
Counter: engine hours run
Counter: engine hours since last service
Counter: engine days since last service
Counter: genset total active energy (kWh)
Counter: genset total inductive reactive energy (kVArh-ind)
Counter: genset total capacitive reactive energy (kVArh-cap)
Counter: remaining engine hours to service-1
Counter: remaining engine days to service-1
Counter: remaining engine hours to service-2
Counter: remaining engine days to service-2
Counter: remaining engine hours to service-3
Counter: remaining engine days to service-3