D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 70 -
067-Genset High
Frequency Warning Limit
If the genset frequency goes over this
limit when feeding the load, this will
generate a GENSET HIGH
FREQUENCY warning.
068-Genset High
Frequency Shutdown
Limit
If the genset frequency goes over this
limit when feeding the load, this will
generate a GENSET HIGH
FREQUENCY shutdown alarm and the
engine will stop.
069-Genset Frequency
Fail Timer
If the genset frequency goes outside of
the limits during this timer, a genset
frequency fault will occur.
070-Low Battery Voltage
Warning Limit
If the battery voltage falls below this
limit, this will generate a LOW
BATTERY warning.
071-Low Battery Voltage
Shutdown Limit
If the battery voltage falls below this
limit, this will generate a LOW
BATTERY shutdown alarm and the
engine will stop.
072-High Battery Voltage
Warning Limit
f the battery voltage goes over this limit,
this will generate a HIGH BATTERY
warning.
073-High Battery Voltage
Shutdown Limit
If the battery voltage goes over this
limit, this will generate a HIGH
BATTERY shutdown alarm and the
engine will stop.
074-Battery Voltage Fail
Timer
If the battery voltage goes outside of the
limits during this timer, a battery voltage
fault will occur.
075-Genset Voltage
Unbalance Limit
If any genset phase voltage differs from
the average more than this limit, it will
generate a Voltage Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
076-Genset Voltage
Unbalance Action
1: shutdown alarm
2: loaddump alarm
3: warning
077-Genset Current
Unbalance Limit
If any genset phase current differs from
the average more than this limit, it will
generate a Current Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
078-Genset Current
Unbalance Action
1: shutdown alarm
2: loaddump alarm
3: warning
079-Genset Reverse
Power Warning Limit
If the genset power is negative and
goes above this limit then a REVERSE
POWER warning will be generated. If
this parameter is set to 0 then reverse
power fault is not monitored.