D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 71 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
080-Genset Reverse
Power Loaddump Limit
kW
0
50000
0
If the genset power is negative and
goes above this limit then a REVERSE
POWER loaddump will be generated.
081-Genset Reverse
Power Fail Timer
sec
0
120
5
If the genset power is negative and over
limits during this timer, a reverse power
fault will occur.
082-Genset Overcurrent
Limit
Amp
0
50000
0
If one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
083-Genset Overcurrent
Limit-2
Amp
0
50000
0
When secondary voltage is selected, if
one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
084-Genset Overcurrent
Limit-3
Amp
0
50000
0
When tertiary voltage is selected, if one
of the genset phase currents goes over
this limit when feeding the load, this will
generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
085-Genset Overcurrent
Action
-
0
3
0
0: shutdown alarm
1: loaddump alarm
086-Overcurrent Time
Multiplier
0
1
64
16
This parameter defines the reaction
speed of the overcurrent detector. A
higher number means higher sensitivity.
Detailed explanation is given at chapter:
“Overcurrent Protection”
087-Genset Overload
Limit
kW
0
50000
0
If the total genset active power goes over
this limit when feeding the load, this will
generate a genset overload loaddump
alarm. If this parameter is set to 0 then
overload fault is not monitored.
088-Genset Overload
Fail Timer
sec
0
120
3
If the genset active power is over the
limit during this timer, an overload fault
will occur.
089-Load Shedding Low
Limit
kW
0
50000
0
If the genset power goes below this limit
then the load shedding relay will be
deactivated. Review chapter “Load
Shedding” for more details.
090-Load Shedding High
Limit
kW
0
50000
0
If the genset power goes above this
limit then the load shedding relay will be
activated. Review chapter “Load
Shedding” for more details.
091-Load Add Delay
sec
0
240
0
This is the minimum delay between 2
load_add pulses. Review chapter “Load
Shedding” for more details.