080-Genset Reverse
Power Loaddump Limit
If the genset power is negative and
goes above this limit then a REVERSE
POWER loaddump will be generated.
081-Genset Reverse
Power Fail Timer
If the genset power is negative and over
limits during this timer, a reverse power
fault will occur.
082-Genset Overcurrent
Limit
If one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
083-Genset Overcurrent
Limit-2
When secondary voltage is selected, if
one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
084-Genset Overcurrent
Limit-3
When tertiary voltage is selected, if one
of the genset phase currents goes over
this limit when feeding the load, this will
generate a genset overcurrent fault
condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
085-Genset Overcurrent
Action
086-Overcurrent Time
Multiplier
This parameter defines the reaction
speed of the overcurrent detector. A
higher number means higher sensitivity.
Detailed explanation is given at chapter:
“Overcurrent Protection”
087-Genset Overload
Limit
If the total genset active power goes over
this limit when feeding the load, this will
generate a genset overload loaddump
alarm. If this parameter is set to 0 then
overload fault is not monitored.
088-Genset Overload
Fail Timer
If the genset active power is over the
limit during this timer, an overload fault
will occur.
089-Load Shedding Low
Limit
If the genset power goes below this limit
then the load shedding relay will be
deactivated. Review chapter “Load
Shedding” for more details.
090-Load Shedding High
Limit
If the genset power goes above this
limit then the load shedding relay will be
activated. Review chapter “Load
Shedding” for more details.
This is the minimum delay between 2
load_add pulses. Review chapter “Load
Shedding” for more details.