EasyManua.ls Logo

Datakom D-100 MK2 - Page 77

Datakom D-100 MK2
123 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 77 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
159-Service-1 Engine
Hours
hours
0
5000
250
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-1
engine hours.
160-Service-1 Period
month
0
24
6
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-1
Period.
161-Service-1 Alarm
Level
-
0
3
3
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
162-Service-2 Engine
Hours
hours
0
5000
250
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-2
engine hours.
163-Service-2 Period
month
0
24
6
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-2
Period.
164-Service-2 Alarm
Level
-
0
3
0
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
165-Service-3 Engine
Hours
hours
0
5000
250
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-3
engine hours.
166-Service-3 Period
month
0
24
6
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-3
Period.
167-Service-3 Alarm
Level
-
0
3
0
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
168-J1939 Enable
-
0
1
0
0: The J1939 port is inoperative.
1: The analog measurements (oil, temp,
and rpm) are picked up from the ECU. If
the ECU communication is lost, then the
engine will be stopped.

Table of Contents