Verify that air flow within the rack, and through the front and rear panel vents of the node, is not obstructed in any way.
Make sure that the faceplate on the affected node is installed, properly seated, and undamaged. In some cases, removing
and re-seating the faceplate will resolve this issue.
Run the isi_hw_status command. Review the output to determine whether there is a slow or failed fan that was not
otherwise reported.
Check for high CPU and disk usage in the node. High usage can contribute to high temperatures within the node.
If the steps above were unsuccessful in clearing this event, the subsystem that monitors the health of the hardware (such as
the temperature and fan speeds) might have encountered a problem. This event can occur intermittently without harm to the
system and you can safely quiet the event unless the issue persists.
If the event persists, gather logs, and then contact Technical Support for additional troubleshooting. For instructions on how to
gather cluster logs, see Gathering cluster logs.
900080001
A sensor in the front panel of a node has exceeded the specified threshold.
Description
This event can occur intermittently without harm to the system.
Administrator action
1. Cancel or quiet the event.
2. If the event recurs, shutdown and restart the node by completing the following steps:
Connect to the affected node through SSH or serial cable.
Shut down the node by running the following command:
shutdown -p now
Wait for the node to shut down, and then disconnect both power supply cables.
Press the power button on the node to discharge any remaining stored power.
Reconnect the power cables and then start the node.
3. (HD400 only.) Re-seat the front panel connector by checking that the ribbon cable is properly attached and properly seated.
4. (All other nodes.) Re-seat the front panel.
5. Move the front panel from a functioning node to the affected node and see if the event clears.
6. Install the front panel from the affected node on another node to determine if the problem is with the front panel or with the
node.
If the problem follows the front panel, contact Technical Support to request a new front panel.
If the above steps do not resolve the issue, gather logs, and then contact Technical Support for additional troubleshooting. For
instructions on how to gather cluster logs, see Gathering cluster logs.
900080002
A power supply fan in the node might have failed.
Description
If the fan speed temporarily falls out of optimal range for less than a minute or so and the event does not repeat, this event
might be a false alarm.
Hardware events
149