Chapter 7 Parameters ASDA-B2
7-46 Revision May, 2018
P1-56 OVW Output Overload Warning Level
Address: 0170H
0171H
Operation
Interface:
Panel/Software Communication
Related Section: N/A
Default: 120
Control
Mode:
ALL
Unit: %
Range: 0 ~ 120
Data Size: 16-bit
Format: Decimal
Settings: The setting value is 0 ~ 100, if the servo motor continuously
outputs the load and is higher than the setting proportion (P1-56),
the early warning for overload (DO is set to 10, OLW) will occur.
If the setting value is over 100, it will disable this function.
P1-57 CRSHA
Motor Crash Protection (Torque
Percentage)
Address: 0172H
0173H
Operation
Interface:
Panel/Software Communication
Related Section: N/A
Default: 0
Control
Mode:
ALL
Unit: %
Range: 0 ~ 300
Data Size: 16-bit
Format: Decimal
Settings: Setup protection level (for the percentage of rated torque, set the
value to 0 means to disable the function, set the value to 1 or
number above means to enable the function).
P1-58 CRSHT Motor Crash Protection Time
Address: 0174H
0175H
Operation
Interface:
Panel/Software Communication
Related Section: N/A
Default: 1
Control
Mode:
ALL
Unit: ms
Range: 0 ~ 1000
Data Size: 16-bit
Format: Decimal
Settings: Setup the protection time:
When it reaches the level, AL.030 occurs after exceeding the
protection time.