Chapter 7 Parameters ASDA-B2
7-82 Revision May, 2018
P3-03
FLT Communication Error Disposal
Address: 0306H
0307H
Operation
Interface:
Panel / Software Communication
Related Section:
8.2
Default: 0
Control
Mode:
ALL
Unit: N/A
Range: 0 ~ 1
Data Size: 16-bit
Format: Hexadecimal
Settings: The definition of the setting value is as the following:
0: Warning and keeps running
1: Warning and stops deceleration (The deceleration time is set to
parameter P1-32)
P3-04
CWD Communication Time Out
Address: 0308H
0309H
Operation
Interface:
Panel / Software Communication
Related Section:
8.2
Default: 0
Control
Mode:
ALL
Unit: sec
Range: 0 ~ 20
Data Size: 16-bit
Format: Decimal
Settings: If the setting value is not 0, enable communication timeout
immediately. If it is set to 0, disable the function.
P3-05 CMM Communication Mechanism
Address: 030AH
030BH
Operation
Interface:
Panel / Software Communication
Related Section:
8.2
Default: 0
Control
Mode:
ALL
Unit: N/A
Range: 0x00 ~ 0x01
Data Size: 16-bit
Format: Hexadecimal
Settings: RS-232 via MOBUS communication or communicate with
ASDA-Soft
RS-232 Communication format
0: RS-232/RS485 via Modbus communication
1: RS-232 upon ASDA-Soft software