DVP-ES3/EX3/SV3/SX3 Series Hardware and Operation Manual
5-14
_5
X0. 0
T0( P V)
Y0. 0
S V: K100
10se c
M0
M1
B. Accumulative timers
When the TMR instruction is executed, the accumulative timer begins to count. When the value of the timer matches
the timer setting value, the output coil is ON. As long as you add the letter S in front of the letter T, the timer
becomes an accumulative timer. When the conditional contact is OFF, the value of the accumulative timer is not
reset. When the conditional contact is ON, the accumulative timer counts from the current value.
When M0=ON and the timer T250 takes 100 ms as the timing unit, the output coil T250 is ON when the value
of the timer = timer setting value 100.
When M0=OFF, the accumulative timer ST250 stops counting, and the value of the timer stays the same.
When M0=ON, the value of the timer is the accumulating value. When the accumulated value = timer setting
value 100, the output coil T250 is ON.