DVP-ES3/EX3/SV3/SX3 Series Hardware and Operation Manual
2-2
2.1 DVP-ES3/EX3 Series
2.1.1 General Specifications
-40 to 70°C
Operating humidity
5–95%
Storage humidity
5–95%
No corrosive gas exists.
Ingress protection
IP20 (NOT UL Certified)
EMC (electromagnetic
Refer to Appendis C for more information.
Vibration resistance
Tested with:
5
Hz ≦ f ≦ 8.4 Hz, constant amplitude 3.5 mm;
8.4 Hz ≦ f ≦ 150 Hz, constant acceleration 1g
Duration of oscillation: 10 sweep cycles
per axis on each direction of the three mutually perpendicular axes
International Standard IEC 61131-2 & IEC 60068-2-6 (TEST Fc)
Shock resistance
Tested with:
Half-sine wave:
Strength of shock 15 g peak value, 11 ms duration;
Shock direction: The shocks in each in direction per axis, on three mutually
perpendicular axes (total of 18 shocks)
International Standard IEC 61131-2 & IEC 60068-2-27 (TEST Ea)
Conforms to IEC 61131-2, UL 61010-2-201, UL508
Ambient air
temperature-barometric
Operating: 1013 ~ 795hPa (0 ~ 2000 m)
Storage:1013 ~ 660hPa (0 ~ 3500 m)