DVP-ES3/EX3/SV3/SX3 Series Hardware and Operation Manual
14-8
Error
Code
(16#)
Description Solution Flag Log
range.
l
1413
The right-side module cannot be
detected.
Check if the right-side module is correctly connected. SM10 V
1414
The number of modules powered is
inconsistent with the the number
checked.
When powered on, check if the automatic comparison
function is enabled or disabled (SM227), and check the
number of expansion points and the number of units set
SM10 V
1420
Initialization error on the left-side
module (number of left-side module
Check the number of modules. SM10 V
l
1424
The communication of the left-side
module times out or the model name
is incorrect.
Check if the module is correctly connected or if the
module is the same as connected.
SM10 V
1425
Memory detection error on the
left-side module.
Check if the module is correctly connected. SM10 V
200A Invalid instruction
Check the program, compile the program again, and
download the program again.
SM5 V
6010
The number of MODBUS TCP
connections exceeds the range.
Check the number of superior devices (maximum is 32).
SM
1092
V
6011
The number of EtherNet/IP
connections exceeds the range.
Check the number of connections (maximum is 16).
SM
V
C000
-
The program syntax is incorrect.
Save the PLC program and hand the file to the company
or the technicians.
- V