VFD-MS300/MH300 EtherNet/IP Communication Card CMM-EIP01
CMM-EIP01 Operation Manual
26
Object Instance Attributes Definition
Initial
value
R/W Size Note
0x300
0x14
Digital input's corresponding CPU pin status;
(refer to Note 3 for parameter 00-04)
0 R U16
0x15
Digital output's corresponding CPU pin status;
(refer to Note 4 for parameter 00-04)
0 R U16
0x16
Motor's actual rotation count (PG card PG1);
when the actual rotational direction is changed
and the drive is stopped, the display on the digital
keypad is reset to zero, and the counter starts at
0. Max. value is 65535
0 R U16
0x17 Pulse input frequency (PG card PG 2) 0 R U16
0x18
Pulse input position (PG card PG 2);
max. value is 65535
0 R U16
0x22
0x19 Tracking error under full position control 0 R U16
0x1A Overload count (0.00–100.00 %) 0 R U16
0x1B GFF's percentage value (%) 0 R U16
0x1C DC bus voltage ripple current (unit: V
dc
) (r.) 0 R U16
0x1D Value of PLC register D1043 (C) 0 R U16
0x1E Magnetic pole section of a synchronous motor 0 R U16
0x1F User physical output 0 R U16
0x20 Parameter 00-05's output value 0 R U16
0x21
Motor's rotation count (retained when stopped;
reset to zero before running)
0 R U16
0x22
Motor's rotation position (retained when stopped;
reset to zero before running)
0 R U16
0x23 Operating speed of VFD cooling fan (%) 0 R U16
0x24
VFD control status 0: Speed mode 1:
Torque mode
0 R U16
0x25 VFD operating carrier wave frequency 0 R U16
0x26 Reserved
0x27 VFD status
0x28 Positive / negative output torque of VFD
0x29 Torque command
0x2A KWH display
0x2B PG2pulse input lower byte
0x2C PG2pulse input upper byte
0x2D Motor's actual position: lower byte
0x2E Motor's actual position: upper byte
0x2F PID reference target
0x30 PID offset
0x31 PID output frequency