44 Pictures for illustrating purposes only
ELECTROVAP MC2 STEAM BATH
Cylinder maintenance guide
for tap or hard waters
• The water tightness is indicated in French grade, the said value is the water hydrotimetric
content (TH).
• The water quality is to be mentioned on your request so that to fit the most appropriate steam
cylinder for the best working of the humidifier.
300 H 800 H
1000 H 2000 H 4000 H
Estimated cylinder maintenance curve
Working hours
X= Humidifier steam demand
Model ELMC 5 to 15-2
ELMC 10 single
phase
ELMC 20 to 90
Length (mm) 160 270 250
Length of the genuine stainless steel electrode plates
During cylinder maintenance (page n° 47), it is recommended to measure the length of the
electrode plates. The latter should be replaced when the lenght is shorter than 1/3 or 1/2 of
the original lenght (s.a. above table).
Example given: it is recommended to maintain (if cleanable type) or change (if disposable type) the
steam cylinder every 800 to 900 hours of operation for a generator running at full capacity and using
a water of TH20.