TECHNICAL REFERENCE MANUAL
3.3.2 Stand-alone mode
Before starting the stand-alone mode, output configuration must be done (See 3.2 Output interfaces on page 9)
3.3.2.1 Auto start configuration
The following steps are necessary to configure the DLS-C(H)/FLS-C(H) for stand-alone mode with auto start.
No. Action Comment Command
1
Set auto start Set the DLS-C(H)/FLS-C(H) to the stand-alone
mode with auto start and with the desired
sample rate.
Example for device 0:
Set sample rate to fastest possible speed.
s0A+0<trm>
1)
1) Commands are described in 9 Command set on page 29
Note: If the serial line settings of the device have been lost, please reset the configuration to the factory settings (8 Factory settings on
page 28) using the reset button (6.2 Reset switch on page 24). Please note that the ID switch must be reset manually.
3.3.2.2 Manual start configuration
Configure the Digital Input (see 9.3.8 Configure digital input (sNDI1) on page 38) to activate the external trigger to start measurements.
No. Action Comment Command
1
Activate digital input DI1 Defines the action for a trigger event on DI1.
Example for device 0:
Configure DI1 to start and stop tracking. If
DI1 is high, distances are measured and the
result is transferred to the output at all
interfaces. If DI1 goes to low, the
measurement stops
s0DI1+3<trm>
1)
2
Save settings The changed configuration must be saved to
make it permanent.
Example for device 0:
Save settings for device 0 s0s<trm>
1)
1) Commands are described in 9 Command set on page 29
Note: If the serial line settings of the device have been lost, please reset the configuration to the factory settings (8 Factory settings on
page 28) using the reset button (6.2 Reset switch on page 24). Please note that the ID switch must be reset manually.
Distance Laser Sensor Page 11/53

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dimetix DLS-C 15 and is the answer not in the manual?

Dimetix DLS-C 15 Specifications

General IconGeneral
BrandDimetix
ModelDLS-C 15
CategoryMeasuring Instruments
LanguageEnglish