CT100 inverter Detailed instructions of function parameters
114
overlaid.
1: valid, clear after power off
2: invalid
3: valid in running, clear after power off
F06.13
Keypad potentiometer
AI0 lower limit
Setting range: 0.00
10.00V
Default value:
0.00V
F06.14
Corresponding setting
of keypad
potentiometer AI0
lower limit
Setting range: -100.0
100.0%
Default value:
0.0%
F06.15
Keypad potentiometer
AI0 upper limit
Setting range: 0.00
10.00V
Default value:
10.00V
F06.16
Corresponding setting
of keypad
potentiometer AI0
upper limit
Setting range: -100.0
100.0%
Default value:
100.0%
F06.17
Keypad potentiometer
AI0 filter time
Setting range: 0.00
10.00s
Default value:
0.10s
F06.18
AI1 lower limit
Setting range: 0.00
10.00V
Default value:
0.00V
F06.19
Corresponding setting
of AI1 lower limit
Setting range: -100.0
100.0%
Default value:
0.0%
F06.20
AI1 upper limit
Setting range: 0.00
10.00V
Default value:
10.00V
F06.21
Corresponding setting
of AI1 upper limit
Setting range: -100.0
100.0%
Default value:
100.0%
F06.22
AI1 input filter time
Setting range: 0.00
10.00s
Default value:
0.10s
F06.23
AI2 lower limit
Setting range: -10.00
10.00V
Default value:
0.00V
F06.24
Corresponding setting
of AI2 lower limit
Setting range: -100.0
100.0%
Default value:
0.0%