EasyManuals Logo

DSC Neo User Manual

DSC Neo
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #221 background imageLoading...
Page #221 background image
Appendix 7: Specifications
l 2-way wireless device support
l Visual verification (images + audio)*
l Proximity tag support
l PGM scheduling
l Quick arming
l User, partition, module, zone and system labels
l Soak test*
l Programmable system loop response
l Keypad and panel software versions viewable through keypad
l Doorbell zone type
l Low battery PGM type
*Feature not evaluated by UL/ULC.
Locating Detectors and Escape Plan
The following information is for general guidance only and it is recommended that local fire codes and regulations be con-
sulted when locating and installing smoke and CO alarms.
Smoke Detectors
Research has shown that all hostile fires in homes generate smoke to a greater or lesser extent. Experiments with typical
fires in homes indicate that detectable quantities of smoke precede detectable levels of heat in most cases. For these reas-
ons, smoke alarms should be installed outside of each sleeping area and on each storey of the home.
The following information is for general guidance only and it is recommended that local fire codes and regulations be con-
sulted when locating and installing smoke alarms.
It is recommended that additional smoke alarms beyond those required for minimum protection be installed. Additional
areas that should be protected include: the basement; bedrooms, especially where smokers sleep; dining rooms; furnace
and utility rooms; and any hallways not protected by the required units. On smooth ceilings, detectors may be spaced 9.1m
(30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement, the presence of joists,
uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-02 or other appropriate national
standards for installation recommendations.
l Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may pre-
vent the unit from detecting smoke.
l Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector
may prevent smoke from entering the unit.
l Do not locate detectors in areas of high humidity.
l Do not locate detectors in areas where the temperature rises above 38ºC (100ºF) or falls below 5ºC (41ºF).
l Smoke detectors should always be installed in USA in accordance with Chapter 11 of NFPA 72, the National Fire
Alarm Code: 11.5.1.1.
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved single- and multiple-sta-
tion smoke alarms shall be installed as follows:
1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a sleeping room, the distance
measured along a path of travel.
3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including basements and excluding crawl
spaces and unfinished attics.
5. In the living area(s) of a guest suite.
6. In the living area(s) of a residential board and care occupancy (small facility).
- 221 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC Neo and is the answer not in the manual?

DSC Neo Specifications

General IconGeneral
ModelDSC Neo
CategorySecurity System
PartitionsUp to 8
TypeHybrid Security System
ZonesUp to 128 zones
CommunicationCellular, IP
CompatibilityPowerG wireless sensors
Remote AccessYes, via app
PGMs4
Wireless RangeUp to 2 km with PowerG
Event Buffer1000 events
Wireless Frequency433 MHz, 868 MHz
Power Supply16.5VAC, 40VA
Battery BackupYes, 12VDC 7Ah
Operating Temperature0°C to 49°C (32°F to 120°F)
Event LogYes

Related product manuals