Section 5: Programming
If a wireless key is used to away arm the system, the door must still be opened then closed to complete the arming
sequence. The indoor siren will activate until the exit delay has expired.
017 24-Hour Burglary
This zone type is active at all times. It reports an alarm if the alarm system is armed or disarmed. This zone type sounds the
siren for the length of Bell time-out if the audible attribute is enabled.
018 24-Hour Bell/Buzzer
When the alarm system is armed and this type of zone is tripped, the siren activates for the duration of the bell time-out. If the
alarm system is disarmed when this type of zone is tripped, the keypad buzzer activates until an access code is entered.
023 24-Hour Supervisory
This zone is active and reports alarms at all times when tripped. The siren and keypad buzzer do not activate.
Note: The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6k, the alarm state is short and the trouble state is open. For use with normally open contacts.
024 24-Hour Supervisory Buzzer
When tripped, the keypad buzzer emits a steady tone until a valid access code is entered.
025 Auto Verify Fire
(Hardwired smoke detectors)
When the zone is activated, a 30-second delay begins but no fire alarm sounds. If the same zone is activated again up to 60
seconds after the delay expires, the alarm is triggered immediately. If the same zone is activated after 60 seconds, the entire
sequence begins again.
If a second fire zone is violated during the auto-verify sequence, both zones a fire alarm is immediately triggered.
(Wireless smoke detectors)
When the zone is activated, a 40-second delay begins. The alarm is triggered if the zone is still faulted after 30 seconds. If
the zone is no longer in alarm, an 80-second verification timer begins. If any fire zone is activated during this period, the
alarm is triggered.
If another fire zone is activated during the auto verify sequence, both zones go into alarm immediately.
Note: Wireless smoke detectors used with this zone type must have a built in siren to act as a pre-alert to the system alarm.
Note: The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6kΩ, the alarm state is short and the trouble state is open.
027 Fire Supervisory
When this zone is tripped, the keypad buzzer activates and a supervisory alarm is sent to the monitoring station. A valid
access code must be entered to silence the buzzer.
Note: The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6k, the alarm state is short and the trouble state is open.
040 24-Hour Gas
Instant alarm when activated, audible alarm at default.This zone type may be assigned to any device type.
041 24-Hour CO
This zone type is used with CO detectors. In the event of an alarm, a distinctive siren cadence is sounded. This is followed by
a 5-second pause and then repeated. After 4 minutes, the 5-second pause is extended to 60 seconds; however, BTO must
be programmed with a value of 5 minutes or higher. The siren is silenced when an access code is entered or the siren times
out.
Note: The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5k6, the alarm state is short and the trouble state is open. For use with normally open contacts.
042 24-Hour Holdup
Instant alarm when activated, silent alarm at default.
Note: Not for use in UL listed installations.
043 24-Hour Panic
Instant alarm when activated, audible alarm at default.
- 66 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC Neo and is the answer not in the manual?

DSC Neo Specifications

General IconGeneral
ModelDSC Neo
CategorySecurity System
PartitionsUp to 8
TypeHybrid Security System
ZonesUp to 128 zones
CommunicationCellular, IP
CompatibilityPowerG wireless sensors
Remote AccessYes, via app
PGMs4
Wireless RangeUp to 2 km with PowerG
Event Buffer1000 events
Wireless Frequency433 MHz, 868 MHz
Power Supply16.5VAC, 40VA
Battery BackupYes, 12VDC 7Ah
Operating Temperature0°C to 49°C (32°F to 120°F)
Event LogYes