EasyManuals Logo

DSC Neo User Manual

DSC Neo
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
Section 5: Programming
04 Bypass Enabled
ON: The zone can be manually bypassed.
OFF: The zone cannot be bypassed.
05 Force Arm
ON: The system can be armed with the zone open. The zone is temporarily bypassed and, when secured, is monitored by
the system.
EN
ON: When open zones cancel arming is enabled [021][7], the system can begin arming with an open, force armable zone,
but if the zone is still open when the exit delay timer expires, the arming will be cancelled.
OFF: The system cannot be armed if the zone is open.
06 Swinger Shut Down
ON: When the zone goes into alarm for the number of times programmed in the Swinger Shutdown Counter ( [377]
Communication Variables), it shuts down with no further transmissions sent to the monitoring station. The siren follows
swinger shutdown if programmed.
OFF: Swinger shutdown is disabled. All alarms are transmitted.
07 Transmission Delay
ON: Reporting of zone alarms is delayed for the programmed time in section 377 (See "[377] Communication Variables" on
page 107). If a valid access code is entered within this time, no alarm signal is communicated.
OFF: When an alarm occurs, the reporting code is transmitted immediately.
08 Burglary Verification
ON: Enabled for cross zoning/police code. Zone alarms are not communicated until a burglary verified event occurs.
OFF: Not enabled for cross zoning/police code.
09 Normally Closed (NC)
ON: The zone requires a normally closed loop.
OFF: The zone follows programming in section [013] option 2.
See note after option 11.
10 Single End of Line (SEOL) Resistors
ON: The zone requires a single end-of-line resistor (5.6K).
OFF: The zone follows programming in section [013] option 2.
See note after option 11.
11 Double End of Line (DEOL)
ON: The zone requires two end-of-line resistors (5.6K).
OFF: The zone follows programming in section [013] option 2.
Note: If more than 1 option is enabled for options 09, 10, and 11 the lowest attribute number takes precedence. If options 09
and 10 are both enabled the zone follows the normally closed loop configuration.
12 Fast Loop/Normal Loop Response
ON: Follows a fast loop response of 50ms.
OFF: Follows a normal loop response as programmed in the Zone Loop Response Time section.
13 2-Way Audio Attribute
ON: Panel is able to initiate a 2 way audio session.
OFF: Only the microphone turns on, initiating a a Listen-in only session. The speaker remains off.
14 Hold Up Verification
ON: An alarm from zones of this type can contribute to a verified hold up alarm. Use this attribute with Panic and Hold Up
zones.
OFF: An alarm from zones of this type does not contribute to a verified hold up alarm. The zone does not cause the hold up
verification timer to start counting down, or generate a verified hold up if the alarm is detected while the timer is running.
- 69 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC Neo and is the answer not in the manual?

DSC Neo Specifications

General IconGeneral
ModelDSC Neo
CategorySecurity System
PartitionsUp to 8
TypeHybrid Security System
ZonesUp to 128 zones
CommunicationCellular, IP
CompatibilityPowerG wireless sensors
Remote AccessYes, via app
PGMs4
Wireless RangeUp to 2 km with PowerG
Event Buffer1000 events
Wireless Frequency433 MHz, 868 MHz
Power Supply16.5VAC, 40VA
Battery BackupYes, 12VDC 7Ah
Operating Temperature0°C to 49°C (32°F to 120°F)
Event LogYes

Related product manuals