12.3 GROUP 3 DEFAULT PARAMETERS
PRIMARY INPUT FULL SCALE VALUE - Group 3
Available: Always
Upper display: Full scale value
Lower display: PI.FSV
Range: from 10 to 99950. Changes to this value affect the values for the pressure input low
scale, the alarm set points and the retransmission limits.
Default value: 10000.
PRIMARY INPUT LOW SCALE VALUE - Group 3
Available: Always
Upper display: Low scale value
Lower display: PI.LSV
Range: from -/+25% of Full scale value
Default value: 0.
PRIMARY INPUT DECIMAL POINT POSITION - Group 3
Available: Always
Upper display: Full scale value
Lower display: PI.DP
Range: Use ▼ ▲ keys to select the position of the decimal point.
Default value: None.
SECONDARY INPUT THERMOCOUPLE TYPE - Group 3
Available: Only if SI.TYP is tc.
Upper display: Selected thermocouple type of temperature input.
Lower display: SI.TC
Range: tc J, tc CA, tc L, tc N. (thermocouple J, thermocouple K (Cromel lumel),
thermocouple L, thermocouple N.)
Default value: Thermocouple J.
ENGINEERING UNIT FOR SECONDARY INPUT - Group 3
Available: Only if SI.TYP is tc or rtd.
Upper display: Selected type of temperature input engineering unit.
Lower display: SI.C/F
Range: Celsius or Fahrenheit
Default value: °F.