UPR700 Microprocessor-Based Pressure/Process Indicator 57
SECONDARY INPUT RANGE LOW - Group 3
Available: Only if SI.TYP is 0-20, 4-20 or 0-10.
Upper display: Secondary input range low.
Lower display: SI.LO
Range: from -1000 to 3000.
Default value: 0.
SECONDARY INPUT RANGE HIGH - Group 3
Available: Only if SI.TYP is 0-20, 4-20 or 0-10.
Upper display: Secondary input range high.
Lower display: SI.HI
Range: from -1000 to 3000.
Default value: 1000.
SECONDARY INPUT DECIMAL POINT POSITION - Group 3
Available: Only when SI.TYP is 0-20, 4-20 or 0-10.
Upper display: Secondary input range high
Lower display: SI.DP
Range: Use keys to select the position of the decimal point.
Default value: None.
ALARM 1 INPUT CHANNEL LINK - Group 3
Available: Always
Upper display: Configuration for alarm 1 selection.
Lower display: A1.LNK
Range: OFF, PrI.In, Sec.In. Disabled, primary input, secondary input.
Default value: Primary input.
ALARM 1 TYPE - Group 3
Available: Only if A1.LNK is different than OFF.
Upper display: Selection of alarm 1 type.
Lower display: A1.TYP
Range: HI, LO, InhIb. High, low, low with mask at start-up.
Default Value: High.
ALARM 2 INPUT CHANNEL LINK - Group 3
Available: Always
Upper display: Configuration for alarm 2 selection.
Lower display: A2.LNK