UPR700 Microprocessor-Based Pressure/Process Indicator 59
MAIN ANALOG OUTPUT RANGE HIGH - Group 3
Available: Only if MO.TYP is different than OFF.
Upper display: Range high for main analog output.
Lower display: MO.HI
Range: from 0 to PI.FSV (if PO.LNK = PrI.In) from -1000 to 3000 (if PO.LNK - SEc.In).
Default value: PI.FSV
SECONDARY ANALOG OUTPUT LINK - Group 3
Available: Only if SO.TYP is different than OFF and SI.TYP is different than OFF.
Upper display: Selected type for second analog output
Lower display: SO.LNK
Range: PrI.In, SEc.In. Primary input, secondary input
Default value: Primary input.
SECONDARY ANALOG OUTPUT RANGE LOW - Group 3
Available: Only if SO.TYP is different than OFF.
Upper display: Range low for second analog output.
Lower display: SO.LO
Range: from 0 to PI.FSV (if SO.LNK = PrI.In) from -1000 to 3000 (if SO.LNK = SEc.In).
Default value: 0.
SECOND ANALOG OUTPUT RANGE HIGH - Group 3
Available: Only if SO.TYP is different than OFF.
Upper display: Range high for second analog output.
Lower display: SO.HI
Range: from 0 to PI.FSV (if SO.LNK = PrI.In) from -1000 to 3000 (if SO.LNK - SEc.In).
Default value: PI.FSV.
SERIAL COMMUNICATION INTERFACE ADDRESS - Group 3
Available: Only if serial communication interface is fitted.
Upper display: Serial communication interface address.
Lower display: SC.ADR
Range: OFF, 1, 2, Ö, 255. Off disables serial interface.
Default value: Off.
PROTOCOL TYPE - Group 3
Available: Only if SC.ADR is different than off.
Upper display: Protocol type.