Range: nodbS, JbuS. Modbus/Jbus selection.
Default value: Modbus.
COMMUNICATION TYPE - Group 3
Available: Only if SC.ADR is different than Off.
Upper display: Number of bits.
Lower display: SC.FRM
Range: 8, 8 E, 8 O. 8 bit without parity, 8 bit + even parity, 8 bit + odd parity.
Default value: 8 bit without parity.
COMMUNICATION BAUD RATE - Group 3
Available: Only if SC.ADR is different than Off.
Upper display: Baud rate.
Lower display: SC.BDR
Range: 600, 1200, 2400, 4800, 9600, 19200.
Default value: 19200.
LOADING DEFAULT DATA - Group 3
Available: Only if access to level 3 is allowed.
Upper display: OFF
Lower display: DEFLT
Range: Use keys to switch the upper display from OFF to On 3, then press FUNC key
to load the default data of the parameters belonging to group 1, group 2, group 3.
12.4 GROUP 4 DEFAULT PARAMETERS
SHUNT CALIBRATION - Group 4
Available: Always
Upper display: OFF if shunt calibration is disabled, On if shunt calibration is enabled.
Lower display: SHUNT
Range: OFF, On.
Default value: On.
SHUNT VALUE - Group 4
Available: Only if SHUNT parameter is on.
Upper display: Shunt value.
Lower display: SHNT.%
Range: From 40.0 to 100.0%
Default value: 80.0%