NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
110
11/04 MN01219002Z-EN
Fault Fault in the hardware Exchange the hardware
A/D convertor
DMI display
DMI clock module
EEPROM
Convertor block
Signal processing
Power supply
Plug-in module 1
Plug-in module 2
Plug-in module 3
Plug-in module 4
Freeze mode active
The DP master has activated
synchronous reading of data inputs
from multiple stations
Intended user action
Function not supported
The DP master has demanded a non-
supported function from the
NZM-XDMI-DPV1
Check the configuration of the
DP master
Ident-number of DP
slave
Contains the identity number of the
NZM-XDMI-DPV1:
hexadecimal 4D11
Initialization running
The NZM-XDMI-DPV1 is in the
initialization phase
Temporary state
Invalid response
DP-slave
The NZM-XDMI-DPV1 has sent an
invalid answer
Check the wiring and the noise
immunity measures
Length of additional
diagnosis information
Contains the length of additional
diagnosis information:
hexadecimal 07
Master lock
The NZM-XDMI-DPV1 is locked by
another DP master
Not used Contains no information for
evaluation
Designation
Meaning Clarification/Hint