PROFIBUS-DPV1 functions
115
11/04 MN01219002Z-EN
Additional acyclic data only with class 2 DPV1
masters
The following functions can be controlled:
State of the DMI outputs (for outputs whose switching signal
has been parameterized to “bus access”, only possible for
operation without class 1 DP master).
Object overview
In DPV1, the acyclic accessed data are compiled to so-called
Process Data Objects. A Process Data Object contains
consistent data contents (data records), which can be
accessed via the DPV1 Read and/or Write services.
The following overview contains all the objects contained in
the NZM-XDMI-DPV1.
Table 19: Process Data Objects in NZM-XDMI-DPV1
Object name
API Slot
number
Index Data
length
(Octets)
Readable
(R)
Writable
(W)
Page
Circuit-breaker
Diagnosis set 1 0 0 1 27 R a 118
Diagnosis set 2 0 0 2 27 R
Diagnosis set 3 0 0 3 27 R
Diagnosis set 4 0 0 4 27 R
Diagnosis set 5 0 0 5 27 R
Diagnosis set 6 0 0 6 27 R
Diagnosis set 7 0 0 7 27 R
Diagnosis set 8 0 0 8 27 R
Diagnosis set 9
0 0 9 27 R
Diagnosis set 10 0 0 10 27 R