PROFIBUS-DPV0 functions
91
11/04 MN01219002Z-EN
Meaning of the data outputs
The data outputs have the following meaning:
Table 8: Data content of the module 1 data outputs
Module 2 conform to PROFIBUS circuit-breaker
profile 2
When this module is selected, the following additional
information can be read out from the circuit-breaker and the
DMI in addition to the information of module 1:
Phase currents I
1
, I
2
and I
3
,
Maximum phase current I
max
.
h
Conformity to the PNO circuit-breaker profile assumes use
of a remote operator with the respective parametric
programming of outputs 4 and 5 in the DMI.
Designation Meaning Precondition
Operation circuit-breaker 00
01
10
11
Do not change state
Switch off
Switch on
Do not change state
Outputs 4 and 5 have been
parameterized in the DMI for
“remote operator”
Output 0 to 5
State of the digital outputs of
the DMI.
The respective output has been
parameterized in the DMI for “bus
access”
Not used No information for
evaluation
h
If a motor starter function is parameterized in the DMI
(only possible in conjunction with the intended circuit-
breaker type -ME), please use module 3 or module 4 if you
control the motor via PROFIBUS-DP or if you wish to be
informed concerning the state of the motor control.