EasyManuals Logo

Eaton NZM3 User Manual

Eaton NZM3
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #163 background imageLoading...
Page #163 background image
NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
158
11/04 MN01219002Z-EN
Assignment of the outputs with remote operator
functions
The following table indicates the possible assignment of
outputs Q4 to Q5 with remote-operator function and the
corresponding value for the Octets 5 to 6 of the Object.
Table 39: Remote operator function and its value
DMI standard display assignment object
This object contains the current standard display assignment
of the DMI.
This object can be read and written (Read, Write). It can be
accessed by class 1 and/or a class 2 DPV1 master.
Intended usage
Use this object in order to obtain information concerning the
current standard display assignment of the DMI or to transfer
a new standard assignment to the DMI.
The standard display of the DMI appears automatically in the
LCD display if the buttons on the DMI have remained in a
non-actuated state for 30 seconds or longer. It is comprised
of six lines where the first four lines are visible on the display.
You can access the other two lines with the
ÍÚ cursor keys.
Value for output
assignment (decimal)
Function Occupy outputs
21 Remote operator Q4, Q5
h
Please note that only the respective value may be
parameterized on the stated outputs with the desired
remote operator function. All stated outputs are to be
parameterized with the same intended value for the
respective remote operator function. If you do not observe
these conditions, you will receive a fault indication when
writing to the object.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton NZM3 and is the answer not in the manual?

Eaton NZM3 Specifications

General IconGeneral
Rated voltage690V AC
TypeMolded Case Circuit Breaker
Trip unitElectronic or Thermal-Magnetic
Number of poles3 or 4 poles
StandardsIEC 60947-2
Rated current250 A, 300 A, 400 A, 500 A, 630 A