DMI
72
11/04 MN01219002Z-EN
Digital outputs (relays)
Number 6
Type of outputs Relays
In groups of 1
Parallel connection of outputs to increase the output Not permissible
Protection for an output relay Miniature circuit-breaker
B16 or fuse 8 A (slow)
Potential isolation from mains supply, inputs Yes
300 V AC (safe isolation)
600 V AC (basic isolation)
Mechanical lifespan (operations)
10 x 10
6
Relay contacts
Conventional thermal current 8A (10 A UL)
Recommended for load . 500 mA, 12 V AC/DC
Protected against short-circuit cos v = 1
16 A characteristic B (B16)
at 600 A
Protected against short-circuit cos v = 0.5 to 0.7
16 A characteristic B (B16)
at 900 A
Rated impulse withstand voltage U
imp
contact coil 6kV
Rated insulation voltage U
i
Rated operational voltage U
e
250 V AC
Safe isolation to EN 50178 between coil and contact 300 V AC
Safe isolation to EN 50178 between contacts 300 V AC
Making capacity
AC-15 250 V AC, 3 A (600 Ops./h) 300000 operations
DC-13 L/R F 150 ms 24 V DC, 1 A (500 Ops./h)
200000 operations
Breaking capacity
AC-15 250 V AC, 3 A (600 Ops./h) 300000 operations
DC-13 L/R F 150 ms 24 V DC, 1 A (500 Ops./h)
200000 operations
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com