Technical data
73
11/04 MN01219002Z-EN
UL/CSA
Filament lamp load 1000 W at 230/240 V AC/
25000 operations
500 W at 115/120 V AC/
25000 operations
Fluorescent tube with ballast
10 x 58 W at 230/240 V AC/
25000 operations
Conventional fluorescent tube, compensated 1 x 58 W at 230/240 V AC/
25000 operations
Fluorescent, uncompensated
10 x 58 W at 230/240 V AC/
25000 operations
Operating frequencies, relays
Mechanical operations 10 million (10
7
)
Mechanical switching frequency 10 Hz
Resistive/lamp load 2 Hz
Inductive load 0.5 Hz
Uninterrupted current at 24 V DC 8 A
DC Control circuit rating codes (utilization category) R300 Light Pilot Duty
Max. rated operational voltage 300 V DC
Max. thermal uninterrupted current at R300 1A
Maximum make/break capacity at R300 28 VA