NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
84
11/04 MN01219002Z-EN
Configuration of the class 1 DP master
In principle you should perform the following steps for the
configuration of the higher-level DP master:
X Add the “Moel4D11.gsd” GSD file to the GSD database of
the configuration tool of your DP master.
X Insert a NZM-XDMI-DPV1 station in the topology of the
bus segment to be configured.
X Assign the station with the intended station address.
X Select one of the four suggested modules for cyclic data
exchange for this station.
– Module 1: Circuit Breaker Profile 1: if you wish to
transfer data conform to profile 1 of the PROFIBUS
circuit-breaker profile,
– Module 2: Circuit Breaker Profile 2: if you wish to
transfer data conform to profile 2 of the PROFIBUS
circuit-breaker profile,
– Module 3: Circuit Breaker Profile 1 and motor starter: if
you wish to transfer data conform to profile 1 of the
PROFIBUS circuit-breaker profile and additional data for
a motor-starter function parameterized in the DMI,
– Module 4: Circuit Breaker Profile 2 and motor starter: if
you wish to transfer data conform to profile 2 of the
PROFIBUS circuit-breaker profile and additional data for
a motor-starter function parameterized in the DMI,
X Repeat steps 2 to 4 for each NZM-XDMI-DPV1 station to
be inserted into the topology.
X Save the configuration.
X Transfer the configuration to the DP master.
h
Observe the documentation of the DP master, when you
perform the configuration.