EasyManua.ls Logo

Eaton NZM3 - Assignment of the Outputs with Motor-Starter Functions; Motor-Starter Function and Its Values

Eaton NZM3
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROFIBUS-DPV1 functions
157
11/04 MN01219002Z-EN
Assignment of the outputs with motor-starter
functions
The following table indicates the possible assignment of
outputs Q0 to Q3 with motor-starter functions and the
corresponding value for the Octets 1 to 4 of the Object.
Table 38: Motor-starter function and its values
Value for output
assignment
(decimal)
Motor-starter function Occupy outputs
17 Direct-on-line starter Q0
18 Reversing starter Q0, Q1
19 Star-delta starter Q0, Q2, Q3
20 Reversing star-delta starter Q0, Q1, Q2, Q3
h
Please note that the motor-starter function can only be
parameterized in conjunction with the circuit-breaker type
-ME which is intended for this purpose. If you do not
observe this, you will receive a fault indication when
writing to the object.
h
Please note that only the respective value may be
parameterized on the stated outputs with the desired
motor-starter function. All stated outputs are to be
parameterized with the same intended value for the
respective motor starter function. If you do not observe
these conditions, you will receive a fault indication when
writing to the object.
h
Information concerning the connection of motor
contactors can be found in a section “Motor starter”,
Page 44.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents