NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
156
11/04 MN01219002Z-EN
04
Trip I
dn
the permissible residual current was exceeded and
has caused a trip
05 Overtemperature the permissible operating temperature of the NZM
electronic circuitry was exceeded and has therefore
caused a trip
06 Overload range 1 the current in at least one phase has 100 % of the
permissible value
07
Overload range 2 the current in at least one phase has reached 120 %
of the permissible value
08 Loud prewarning the current in at least one phase has exceeded 70 %
of the permissible value
09 Unbalance an unsymmetrical phase current load exists
10 Parameter
comparison
the parameters in DMI (parameters used) and NZM
(locally set parameters) differ
11
Trip a trip has occurred (independent of the trip cause)
12 Alarm an alarm state has occurred (independent of the
alarm cause)
13 Motor prot. the circuit-breaker (type -ME) detects an overload
and asks the DMI to disconnect the motor. If the
overload continues, the circuit-breaker will trip.
14
Bus access the output is switched via the PROFIBUS-DP
15
Off the output is permanently deactivated
16 On if the output is permanently activated
Value for output
assignment
(decimal)
Switching signal Output switches, if