NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
124
11/04 MN01219002Z-EN
Status[36] Bit 3 Trip via N-pole
Bit 4 to Bit 7 Not used
Octet 26
2)
Phase issuing alarm
Bit 0 to Bit 3 Not used
Status[45] Bit 4 Alarm from L1
Status[46] Bit 5 Alarm from L2
Status[47] Bit 6 Alarm from L3
Status[48] Bit 7 Alarm from N-pole
Octet 27
1)
Fault states
Status[49] Bit 0 NZM fault: A/D convertor
Status[50]
Bit 1 NZM fault: Signal processing
Status[51] Bit 2 NZM fault: Convertor block
Status[52] Bit 3 NZM fault: EEPROM
Status[53] Bit 4 NZM plug in module 1 fault
Status[54] Bit 5 NZM plug in module 2 fault
Status[55] Bit 6 NZM plug in module 3 fault
Status[56] Bit 7 NZM plug in module 4 fault
1) Prerequisite: Parameter is supported by the connected circuit-breaker,
otherwise “Not used”.
2) The meaning is relevant when the respective Bit is set.
3) With a short-circuit (Trip I
i
) the tripping phase and the phase status cannot be
identified with certainty.
Variable access
(example)
Data position Meaning