NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
126
11/04 MN01219002Z-EN
Octet 8
Bit 4 to Bit 7 Second, 10 position digit –
Bit 0 to Bit 3 Second, 1 position digit
Octet 9
Bit 4 to Bit 7 Millisecond, 100 position
digit
Bit 0 to Bit 3 Millisecond, 10 position
digit
Octet 10
Bit 4 to Bit 7 Millisecond, 1 position digit
Bit 0 to Bit 3 Day of the week Value 0 complies with not
used
Value 1 complies with
Sunday
Value 2 complies with
Monday
Value 7 complies with
Saturday
h
A diagnosis record can also be saved in the circuit-breaker
without an event time. This is always the case when a DMI
was not connected to the circuit-breaker at the time of the
event. In this case, all 8 Octets of the data content event
time are assigned with the value “0”.
h
Octets 9 and 10 always have the value “0”, as the internal
clock of the DMI does not support millisecond and day of
the week.
Data
position
Meaning Explanation
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com