NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
160
11/04 MN01219002Z-EN
Table 40: Address location and meaning of the object data
content
The following table indicates the possible assignment of
lines 1 to 6 as the standard display of the DMI and the
corresponding value for the Octets 1 to 6 of the Object.
Table 41: Display content and their values
Variable access
(example)
Data position Meaning
a table 41
DMI_Standard_Display[1] Octet 1 Assignment line 1
DMI_Standard_Display[2]
Octet 2 Assignment line 2
DMI_Standard_Display[3] Octet 3 Assignment line 3
DMI_Standard_Display[4] Octet 4 Assignment line 4
DMI_Standard_Display[5] Octet 5 Assignment line 5
DMI_Standard_Display[6] Octet 6 Assignment line 6
Value for standard
display
assignment
(decimal)
Meaning, displayed in the selected
line:
00 No display
01 Parameter used: I
r
02 Parameter used: I
i
03 Parameter used: Is
d
04 Parameter used: I
dn
05 Parameter used: T
r
06 Parameter used: T
sd
07 Parameter used: T
vdn
08 Parameter used: I
2
t
09
Current value: I
1rms
10 Current value: I
2rms
11 Current value: I
3rms