DMI
70
11/04 MN01219002Z-EN
Oscillations (IEC 60068-2-6)
10 to 57 Hz
(constant amplitude 0.15 mm)
57 to 150 Hz
(constant acceleration 2 g)
Shock (IEC 60068-2-27)
18 shocks (semi-sinusoidal 15 g/11 ms)
Drop (IEC 60068-2-31) Drop height
50 mm
Free fall, when packed (IEC 60068-2-32) 1 m
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD),
(IEC/EN 61000-4-2, severity level 3)
8 kV air discharge
6 kV contact discharge
Electromagnetic fields (RFI), (IEC/EN 61000-4-3) Field strength 10 V/m
Radio interference suppression (EN 55011, EN 55022) Limit class B
Burst (IEC/EN 61000-4-4, severity level 3) 2 kV power cables,
2 kV signal cables
Immunity to line-conducted interference (IEC/EN 61000-4-
6)
10 V
Dielectric strength
Measurement of air clearances and creepage distances EN 50178, UL 508, CSA C22.2, No 142
Dielectric strength EN 50178
Tool and cable cross-sections
Solid min. 0.2 mm
2
, max. 4 mm
2
/
AWG: 22 – 12
Flexible with ferrule min. 0.2 mm
2
, max. 2.5 mm
2
/
AWG: 22 – 12
Factory wiring: to AWG 30
Width of slot-head screwdriver
3.5 x 0.8 mm; 0.14 x 0.03j
Tightening torque 0.6 Nm
Backup/accuracy of real-time clock
Clock battery backup
at 25 °C/77 °F Normally 64 h
at 40 °C/104 °F Normally 24 h
Accuracy of real-time clock
Normally g 5 s/day, ~ g 0.5 h/year