Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 237
6 2 Digital Outputs Bits 0-7 = Outputs for the fifth digital output card
Bits 8-15 = Outputs for the sixth digital output card
8 2 Digital Outputs Bits 0-7 = Outputs for the seventh digital output card
Bits 8-15 = Outputs for the eighth digital output card
10 16 Analog Outputs 8 Output words of data for 8 analog outputs
Output Instance 127 (0x7F): Extended Motor Starter 2 with Basic Analog and Digital Outputs
Length = 8 Bytes
Byte
Offset
Size
(bytes) Name Description
0 2 Extended Motor
Starter 2 with Basic
Analog and Digital
Outputs
Extended Motor Starter 2 bits
(Byte 1: NETCTRL_CONTROL)
(Byte 2: BCM_Field_Outputs)
Bit 0: Run1
Bit 1: Run2
Bit 2: Reserved
Bit 3: Fault Reset
Bit 4: Control From Network / Switch to Remote
Bit 5: Test Trip
Bit 6: Reserved
Bit 7: Reserved
Bit 8: Output#1 (Conditional. Depends on Operation Mode)
Bit 9: Output#2 (Conditional. Depends on Operation Mode)
Bit 10: Output#3 (Conditional. Depends on Operation Mode)
Bits 11-15: Reserved
2 2 Digital Outputs Bits 0-7 = Outputs for the first digital output card
Bits 8-15 = Outputs for the second digital output card
4 4 Analog Outputs 2 Output words of data for 2 analog outputs
Output Instance 126 (0x7E): Basic Output Control with Extended Analog and Digital Outputs, continued
Length = 26 Bytes
Byte
Offset
Size
(bytes) Name Description