Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
1 1 (0x1) Get/Set BYTE Trip Enable Bit Field Enabling bits for tripping.
Bit location - condition
0 - under voltage
1 - over voltage
2 - Reserved
3 - ground current warning
4 - current phase loss
5 - current unbalance
6 - instantaneous over current
7 - jam
8 - PF deviation
9 - voltage phase loss
10 - voltage unbalance
11 - freq deviation fast
12 - freq deviation slow
13 - under current
14 - high power
15 - low power
16 - Reserved
17 - exceeds starts limit
18 - overload
19 - stall
20 - phase rotation mismatch
21 - PTC
22 - under voltage restart
23 - peak demand
24 - HRGF pulse detection
2 2 (0x2) Get/Set BYTE Warn Enable Bit Field Enabling bits for warning.
Bit location - condition
0 - under voltage
1 - over voltage
2 - Reserved
3 - ground current warning
4 - current phase loss
5 - current unbalance
6 - instantaneous over current
7 - jam
8 - PF deviation
9 - voltage phase loss
10 - voltage unbalance
11 - freq deviation fast
12 - freq deviation slow
13 - under current
14 - high power
15 - low power
16 - Reserved
17 - exceeds starts limit
18 - overload
19 - stall
20 - phase rotation mismatch
21 - PTC
22 - under voltage restart
23 - peak demand
24 - HRGF pulse detection
3 3 (0x3) Get/Set UINT Alarm Debounce Time Alarm Debounce Time
4 4 (0x4) Get/Set BOOL Global Auto Reset Enable (Boolean) If disabled, no auto reset; if enabled, auto reset based on
trip auto-reset bits
Table 108. Motor Protection Object—Class 0xA2 (162), continued