Appendix COptional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 281
Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
5 5 (0x5) Get/Set BYTE Auto reset enable capability for each trip
bit
Per tripping type auto reset enable bits.
Bit location - condition
0 - under voltage
1 - over voltage
2 - Reserved
3 - ground current fault
4 - current phase loss
5 - current unbalance
6 - instantaneous over current
7 - jam
8 - PF deviation
9 - voltage phase loss
10 - voltage unbalance
11 - freq deviation fast
12 - freq deviation slow
13 - under current
14 - high power
15 - low power
16 - Reserved
17 - exceeds starts limit
18 - overload
19 - stall
20 - phase rotation mismatch
21 - PTC
22 - under voltage restart
23 - peak demand
24 - HRGF pulse detection
6 6 (0x6) Get/Set UINT Reset time delay. The amount of time to
wait until we do an auto reset.
Time delay before auto-reset
7 7 (0x7) Get/Set BOOL Perform reset on power up. Protection allowed after delay since start
8 8 (0x8) Get/Set UINT Motor State time delay after which the
RUN state is declared if not reached via
current thresholds.
Motor State time delay after which the RUN state is
declared if not reached via current thresholds.
9 9 (0x9) Get/Set BOOL Start inhibited protection enable when
motor is up to speed.
If enabled, only allows protection when motor is up to
speed
10 10 (0xA) Get/Set UINT Phase Rotation Phase Rotation
11 11 (0xB) Get/Set UINT Protection Instantaneous Overcurrent Trip
Level
Protection Instantaneous Overcurrent Trip Level
12 12 (0xC) Get/Set UINT Protection Instantaneous Overcurrent
Debounce
Protection Instantaneous Overcurrent Debounce
13 13 (0xD) Get/Set UINT Protection Instantaneous Overcurrent
Alarm Level
Protection Instantaneous Overcurrent Alarm Level
14 14 (0xE) Get/Set UINT Protection Instantaneous Overcurrent
Start Delay
Protection Instantaneous Overcurrent Start Delay
15 15 (0xF) Get/Set USINT Protection UnderCurrent Trip Level Protection UnderCurrent Trip Level
16 16 (0x10) Get/Set UINT Protection UnderCurrent Trip Debounce Protection UnderCurrent Trip Debounce
17 17 (0x11) Get/Set USINT Protection UnderCurrent Alarm Level Protection UnderCurrent Alarm Level
18 18 (0x12) Get/Set USINT Protection I Unbalance Trip Percent Level Protection I Unbalance Trip Percent Level
19 19 (0x13) Get/Set UINT Protection I Unbalance Trip Debounce
Time
Protection I Unbalance Trip Debounce Time
20 20 (0x14) Get/Set USINT Protection I Unbalance Alarm Percent
Level
Protection I Unbalance Alarm Percent Level
21 21 (0x15) Get USINT I Phase Loss Trip Level in percent I Phase Loss Trip Level in percent
22 22 (0x16) Get UINT I Phase Loss Debounce I Phase Loss Debounce
Table 108. Motor Protection Object—Class 0xA2 (162), continued