Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 317
400 Proof Test Status UINT8 RO
Default: 0
Enum
Proof Test Status. 0: Proof test is idle (not triggered), 1: Proof test is
running, 2: Proof test passed, 3: Proof test failed.
401 Ground Fault Current Scale
Factor
UINT16 RO
Default: 1000
Ground Fault Current Fractional Scale Factor
Divide integer ground current value by this value to convert the value to
Amps.
402 Ground Current Percent UINT16 RO
Units: Scaled Amps
Ground current percent of trip threshold
Ground current percent of trip threshold
403 GFM CT Diagnostic Status UINT8 RO
Enum
CT input connection diagnostic status passed to BCM: Disabled, OK,
High-Z, Low-Z. GFM CT connection diagnostic status.
500 FLA Active Motor Scaled UINT16 RO
Default: 101 (RW)
Range: 1 to 65535 (RW)
Units: scaled A
Active Overload FLA (Nominal Current) Scaled is a read only parameter
indicating the active FLA. For example, if the application has two
windings (and two FLA settings), this parameter will indicate the currently
active motor winding setting. Scaled by parameter “I Scale Factor”.
501 Rated Speed RPM Active UINT16 RO
Default: 1750
Range: 300 to 3600
Units: RPM
RPM nameplate rating of the active motor winding.
502 Rated HP Active Scaled UINT32 RO
Units: HPx100
HP nameplate rating of the active motor winding. This value is scaled by
0.01. For example if the motor is rated at 123.25 HP then this parameter
should contain 12325.
504 Rated Watts Active UINT32 RO
Default: 14914
Range: 10 to 3728500
Units: W
Watts nameplate rating of the active motor winding.
506 Active Control Source UINT8 RO
Enum
The control source that is currently active: User Interface, Fieldbus or
Fieldwire
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Value Description
0 Proof test is idle (not triggered)
1 Proof test is running
2 Proof test passed
3 Proof test failed
Value Description
0 GFM CT connection diagnostics are disabled
1 GFM CT connection status is good
2 GFM CT connection status is open
3 GFM CT connection status is shorted
255 GFM CT calibration is missing
Value Description
0 No active control source
1 User Interface is the active control source
2 FieldBus is the active control source
3 FieldWire is the active control source
4 User Logic is the active control source