Appendix D—Modbus Register Map
318 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
600 Fieldbus Motor Control BYTE RW
Bitfield
USB Lock
Fieldbus Motor Control - Run 1 Command Bit: This bit is Profile dependent.
For example, this is the Run bit for a FVNR motor application or the Run
FWD bit for a FVR applications. - Run 2 Command Bit: This bit is Profile
dependent. For example, this is not used for a FVNR motor application or
is the Run REV Run for a FVR applications. - Fault Reset: This resets an
active fault if the fault condition is no longer present. - Test Trip: This
allows the user to trip the unit for test purposes. Use Fault Reset to reset
the test trip condition.
601 Output Control BYTE RW
Bitfield
ON / OFF Control for Available Base Control Module Field Outputs. The
Profile type dictates which of these outputs are available as general
purpose outputs. For example, Outputs 2 and 3 are available when the
Direct profile is selected, while only Output 3 is available when the
Reverser Profile is selected. The bits are assigned to specific physical
outputs in the Operation Mode category and the parameters are called
Output x Function Select.
602 Remote Feedback Signal
Parameter
BYTE RW
Bitfield
This parameter only applies if the Operation mode being used includes
digital feedback (Solenoid, MCCB Actuation and Contactor Feeder) and
the selection for the Feedback Signal Source Select parameter is
“Feedback Signals Provided by Network”. If both of these conditions are
met, then this parameter is a read only parameter that allows monitoring
the state of the inputs with this software. Inputs 2 and 3 indicate the
following based on the operation mode. Solenoid: Input 2 (bit 1) = Open,
Input 3 (bit 2) = Closed Contactor/Feeder: Input 2 (Bit 1) = AUX On MCCB
Feeder: Input 2 (Bit 1) = CB On, Input 3 (Bit 2) = CB Alarm
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Bit Description Coil
0 Run1 command bit 9585
1 Run2 command bit 9586
2 Switch Control To Remote 9587
3 Reset fault bit 9588
4 Reserved bit 9589
5 Test trip the device bit 9590
Bit Description Coil
0Bit 0 9601
1Bit 1 9602
2Bit 2 9603
3Bit 3 9604
Bit Description Coil
0 Network feedback input I1 9617
1 Network feedback input I2 9618
2 Network feedback input I3 9619
3 Network feedback input I4 9620
4 Network feedback input I5 9621
5 Network feedback input I6 9622
6 Network feedback input I7 9623
7 Network feedback input I8 9624