Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 411
6006 User Interface USB Modbus
Timeout
UINT16 RW NV
Default: 0
Units: ms
Backup Mem
The time before Modbus communications are considered lost. Every valid
message received will reset this timer. The timeout is in milliseconds.
When this timer expires, communication loss behavior will be triggered.
A value of zero (0) will disable the communication timeout.
6007 Modbus TCP Timeout UINT16 RW NV
Default: 2000
Units: ms
Config CRC
Admin Lock
USB Lock
The time before Modbus TCP communications are considered lost.
Every valid message received will reset this timer. The timeout is in
milliseconds. When this timer expires, communication loss behavior will
be triggered. A value of zero (0) will disable the communication timeout.
6008 Webservices
Communication Timeout
UINT16 RW NV
Default: 0
Units: ms
Config CRC
Admin Lock
USB Lock
The time before HTTP REST communications are considered lost. Every
valid poll assembly message received will reset this timer. The timeout is
in milliseconds. When this timer expires, communication loss behavior
will be triggered. A value of zero (0) will disable the communication
timeout.
6010 Present IP Address UINT8 RO
Array size: 4
The Active IP Address being used on the Network.
Array of 2 registers
6012 Present Subnet Mask UINT8 RO
Array size: 4
The Active Subnet Mask IP Address being used on the Network.
Array of 2 registers
6014 Present Gateway UINT8 RO
Array size: 4
The Active Default Gateway IP Address being used on the Network.
Array of 2 registers
6016 Stored IP Address UINT8 RW NV
Array size: 4
Default: 0xFE, 0x01, 0xA8,
0xC0
Config CRC
Admin Lock
USB Lock
The IP address used in the NV address select configuration. The DIP
switch settings on the Base Control Module determine if a static IP
address of 192.168.1.x, where x= the value on the DIP switch settings is
used, or if DHCP is used or if the IP address stored at this parameter is
used. To use this IP address, enter an IP address for this parameter,
power down the C445, set the DIP switches for the NVMEM selection and
when the unit is powered again, the C445 Ethernet module will be using
this IP address.
Array of 2 registers
6018 Stored Subnet Mask UINT8 RW NV
Array size: 4
Default: 0x00, 0xFF, 0xFF,
0xFF
Config CRC
Admin Lock
USB Lock
The IP subnet mask used in the NV address select configuration. If the
DIP switches on the Base Control Module are set for NVMEM, this IP
subnet mask will take effect following a power cycle.
Array of 2 registers
6020 Stored Gateway UINT8 RW NV
Array size: 4
Default: 0x01, 0x01, 0xA8,
0xC0
Config CRC
Admin Lock
USB Lock
The IP default gateway used in the NV address select configuration.
Array of 2 registers
6022 Ethernet Port 1 Speed
Select
UINT16 RW NV
Default: 100
Enum
Units: Mbs
Config CRC
Admin Lock
USB Lock
Select the Ethernet link speed. Only used when Auto-Negotiate is
disabled.
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Value Description
10 10 Mbps
100 100 Mbps