3 Commissioning
3.1 Hardware enable signal
CANopen for DA1, DC1, DE11 09/16 MN040019EN www.eaton.com 15
3 Commissioning
3.1 Hardware enable signal
A hardware enable signal may be required depending on parameter P-15
(on DC1 and DE11 units) or P1-13 (on DA1 units).
→
Carry out all the commissioning work for the variable frequency
drive/variable speed starter as described in manual
MN04020005Z-EN (for DA1), MN04020003Z-EN (for DC1),
or MN040011EN (for DE11).
→
Check the settings and installations for the connection to the
CANopen network which are described in this manual.
NOTICE
Make sure that starting the motor will not put anyone or
anything in danger. Disconnect the driven machine if there is a
danger in an incorrect operating state.
L
Figure 7: Hardware enable (left: DA1, center: DC1, right: DE11)
→
By default, DC1 variable frequency drives and DE11 variable
speed starters require for an enable signal to be applied.
In the case of DA1 variable frequency drives, the STO
connection needs to be wired.
2
DI1
EN
+24 V
12
STO
7
0 V
13
STO
1
+24 V Out
< 100 mA
2
DI1
EN
+24 V
1
+24 V Out
< 100 mA
1
DI1
EN
+10 V
+10 V Out
< 100 mA