4 CANopen communication settings
4.5 Object directory
CANopen for DA1, DC1, DE11 09/16 MN040019EN www.eaton.com 27
4.5 Object directory
4.5.1 EDS file
PowerXL devices can be integrated into a CANopen structure by using a
standardized EDS (Electronic Data Sheet) file. EDS describes the
functionality of a CANopen device in a machine-readable format. EDS files
list all objects, the supported baud rates, the manufacturer, and other
information as well.
The object dictionary contains all the objects corresponding to a CANopen
module. Objects are used to map a device‘s functionality/parameters.
They are accessed with SDOs or PDOs. As per the corresponding
specification, the object dictionary is subdivided into the following ranges:
Table 14: Object dictionary ranges
The object dictionary contains the entries described below.
4.5.2 Transmission Type
There are four transmission options available.
Table 15: CANopen transmission options
To get the latest version of the EDS file for your device, please
download it from the Eaton FTP server:
https://es-assets.eaton.com/DRIVES/POWERXL/04_CANopen/
Range Description
00 00hex…1F FFhex Communication-specific objects (from DS-301)
20 00hex…5F FFhex Manufacturer-specific objects (the variable frequency drive‘s parameters)
Transmission
Type
Mode Description
0 Acyclical – synchronous Transmissions will only be sent if a SYNC comes
and process data has changed.
1 - 240
Cyclical – synchronous Transmissions will be sent and received after every
nth SYNC.
254
Asynchronous – manufacturer-
specific
The value in the default settings.
Transmissions will only be sent if a value has been
received and something has changed.
Received data will be processed directly.
255
Asynchronous – device profile-
specific
Transmissions will be sent directly if there is a
change.
Received data will be processed directly.
When the device is running with its default configuration, the
value will be set to 254 (“asynchronous – manufacturer-
specific”).