82 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Chapter 6 — PID Application
Feedforward
Table 111. Basic — P8.5.1
Code Parameter Min. Max. Unit Default ID Note
P8.5.1.1

PID2 Feedforward Func 0 1400 See Par ID 1330
P8.5.1.2
PID2 Feedforward Gain -1000.0 1000.0 % 100.0 1401
Table 112. Feedforward 1 — P8.5.2
Code Parameter Min. Max. Unit Default ID Note
P8.5.2.1

PID2 Feedforward 1 Source 0 1402 0 = Not Used
1 = AI1
2 = AI2
3 = Slot A: AI1
4 = Slot B: AI1
5 = FB Process Data Input 1
6 = FB Process Data Input 2
7 = FB Process Data Input 3
8 = FB Process Data Input 4
9 = FB Process Data Input 5
10 = FB Process Data Input 6
11 = FB Process Data Input 7
12 = FB Process Data Input 8
13 = PT100 Temperture
14 = PID1 Output
15 = SlotA PT100 Temp Channel 1
16 = SlotA PT100 Temp Channel 2
17 = SlotA PT100 Temp Channel 3
18 = SlotB PT100 Temp Channel 1
19 = SlotB PT100 Temp Channel 2
20 = SlotB PT100 Temp Channel 3
21 = FB PID2 Feedforward 1
22 = FB PID2 Feedforward 2
P8.5.2.2
PID2 Feedforward 1 Min -200.00 200.00 % 0.00 1403
P8.5.2.3
PID2 Feedforward 1 Max -200.00 200.00 % 100.00 1404
Table 113. Feedforward 2 — P8.5.3
Code Parameter Min. Max. Unit Default ID Note
P8.5.3.1

PID2 Feedforward 2 Source 0 1405 See Par ID 1402
P8.5.3.2
PID2 Feedforward 2 Min -200.00 200.00 % 0.00 1406
P8.5.3.3
PID2 Feedforward 2 Max -200.00 200.00 % 100.00 1407
Table 114. Fire Mode — P9
Code Parameter Min. Max. Unit Default ID Note
P9.1

Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P9.2

Fire Mode Ref Select Function 0 536 0 = Fire Mode Min Frequency
1 = Fire Mode Ref
2 = Fieldbus Ref
3 = AI1
4 = AI2
5 = AI1 + AI2
6 = PID1 Control Output
7 = PID2 Control Output
P9.3
Fire Mode Min Frequency See Par ID 101 See Par ID 102 Hz 15.00 537
P9.4
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P9.5
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P9.6 Fire Mode Test Enable 2443 See Par ID 1346
P9.7

Smoke Purge Frequency 0.0 100.0 % 50.0 554
ote:N
Parameter value can only be changed after the drive has stopped.
Parameter value will be set to be default when changing macros.
Input function is Level sensed.